Guangzhou HongCe Equipment Co., Ltd.

We provide you with industry leading test equipment, advanced online system and solutions–anywhere in the world.

Manufacturer from China
Verified Supplier
12 Years
Home / Products / Helium Leak Testing Equipment /

Automatic Vacuum Chamber Helium Leak Detection System for SF6 Thin Shell Switch Gears 1.0E-6mbar.l/s

Contact Now
Guangzhou HongCe Equipment Co., Ltd.
Visit Website
City:guangzhou
Province/State:guangdong
Country/Region:china
Contact Person:MsTessa Huang
Contact Now

Automatic Vacuum Chamber Helium Leak Detection System for SF6 Thin Shell Switch Gears 1.0E-6mbar.l/s

Ask Latest Price
Video Channel
Brand Name :HongCe
Model Number :L-Z-1×1500
Certification :Third party calibration certificate(cost additional)
Place of Origin :China
MOQ :1 set
Payment Terms :L/C, D/A, D/P, T/T, Western Union, MoneyGram
Delivery Time :120 days
Packaging Details :Plywood
Price :Negotiatable
Cycle time :1hour/pcs
Leak rate :1.0E-6mbar.l/s
Helium leak detector :Inficon
PLC :Omron
more
Contact Now

Add to Cart

Find Similar Videos
View Product Description

Automatic Vacuum Chamber Helium Leak Test and SF6 Charging Rig for SF6 Thin Shell Switch Gears

The stainessless thin shell shall be filled with SF6 gas, no leak is permitted. As there might have welding defects, it is necessary to do leak test before SF6 fill. The normal solution is auto helium leak test system.

As the stainessless thin shell can only bear limited pressure difference, the helium leak test, dryness test and SF6 fill process are completed inside a integrated system, pressure difference of inside & outside of thin shell is controlled by a precise pressure.

Test Concept

Automatic Vacuum Chamber Helium Leak Detection System for SF6 Thin Shell Switch Gears 1.0E-6mbar.l/s

  • Evacute the vacuum chamber.

  • Check the pressure drop inside the product for gross leak test.

  • Evacuate the product and charge helium into the product.

  • Test the helium signal from the vacuum chamber by the leak detector for fine leak judge.

  • Recover helium from the product.

  • Charge SF6 into the product.

  • Vent vacuum chamber.

Technical specification:

  • Cycle time:1hour/pcs.

  • Leak rate:1.0E-6mbar.l/s

  • Test pressre:0.5bar

Main parts of system

Vacuum pump Leybold
Vacuum sensor Inficon
Helium leak detector Inficon
Presure sensor GE
Solenoid valve Burkert
PLC Omron
HMI Omron

Other Esle Helium Leak Test Machine for SF6 Thin Shell Switch

Automatic Vacuum Chamber Helium Leak Detection System for SF6 Thin Shell Switch Gears 1.0E-6mbar.l/s

Paten Certificate:

Automatic Vacuum Chamber Helium Leak Detection System for SF6 Thin Shell Switch Gears 1.0E-6mbar.l/s Automatic Vacuum Chamber Helium Leak Detection System for SF6 Thin Shell Switch Gears 1.0E-6mbar.l/s

International Cooperation:

Automatic Vacuum Chamber Helium Leak Detection System for SF6 Thin Shell Switch Gears 1.0E-6mbar.l/sAutomatic Vacuum Chamber Helium Leak Detection System for SF6 Thin Shell Switch Gears 1.0E-6mbar.l/s

Inquiry Cart 0